General Device and Feedback Monitoring Configuration

Chapter 5

Table 8 - Encoder Resolution 1024 lines/rev

Table 9 - Encoder Resolution 3000 lines/rev

Table 10 - Encoder Resolution 5000 lines/rev

Overspeed Response Time, P24
(OverSpd Response) Setting

Speed (RPM)

1

10

100

1000

10,000

11,718.75

42

2.445

2.475

2.775

5.775

35.775

41.504

48

1.222

1.237

1.387

2.887

17.887

20.752

60

0.611

0.619

0.694

1.444

8.944

10.376

84

0.306

0.309

0.347

0.722

4.472

5.188

132

0.153

0.155

0.173

0.361

2.236

2.594

228

0.076

0.077

0.087

0.180

1.118

1.297

420

0.038

0.039

0.043

0.090

0.559

0.648

Overspeed Response Time, P24
(OverSpd Response) Setting

Speed (RPM)

1

10

100

1000

4000

42

0.837

0.867

1.167

4.167

14.167

48

0.418

0.433

0.583

2.083

7.083

60

0.209

0.217

0.292

1.042

3.542

84

0.105

0.108

0.146

0.521

1.771

132

0.052

0.054

0.073

0.260

0.885

228

0.026

0.027

0.036

0.130

0.443

420

0.013

0.014

0.018

0.065

0.221

Overspeed Response Time, P24
(OverSpd Response) Setting

Speed (RPM)

1

10

100

1000

2400

42

0.503

0.533

0.833

3.833

8.500

48

0.252

0.267

0.417

1.917

4.250

60

0.126

0.133

0.208

0.958

2.125

84

0.063

0.067

0.104

0.479

1.063

132

0.031

0.033

0.052

0.240

0.531

228

0.016

0.017

0.026

0.120

0.266

420

0.008

0.008

0.013

0.060

0.133