Rockwell Automation Publication 750-RM001F-EN-P - February 2012

Chapter 9

Safe Maximum Speed and Direction Monitoring

Max Speed, Max Accel, and
Direction Monitoring
Parameter List

Set these parameters to configure Safe Maximum Speed, Safe Maximum
Acceleration, and Safe Direction Monitoring.

Fi

le

Gr

ou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta T

ype

HOST GROUPS

Feedback

30

Fbk 1 Polarity
Feedback 1 Polarity
Defines the direction polarity for encoder 1.

Default:
Options:

0 = “Normal”
0 = “Normal” (Same as encoder)
1 = “Reversed”

RW 8-bit

Integer

35

Fbk 2 Polarity
Feedback 2 Polarity
Defines the direction polarity for encoder 2.

Default:
Options:

0 = “Normal”
0 = “Normal” (Same as encoder)
1 = “Reversed”

RW 8-bit

Integer

Fe

edback

42

Direction Mon
Direction Monitoring
Defines the allowable direction if Safe Direction Monitoring is enabled.
“Pos Always” (1) – Positive always
“Neg Always” (2) – Negative always
“Pos in SLS” (3) – Positive during safe limited speed monitoring
“Neg in SLS” (4) – Negative during safe limited speed monitoring

Default:
Options:

0 = “Disabled”
0 = “Disabled”
1 = “Pos Always”
2 = “Neg Always”
3 = “Pos in SLS”
4 = “Neg in SLS”

RW 8-bit

Integer

43

Direction Tol
Direction Tolerance
The position limit in encoder units tolerated in the wrong direction when Safe Direction
Monitoring is active.
Units are based on rotary or linear configuration defined by P29 [Fbk 1 Units].

Units:

Default:
Min/Max:

Deg
mm
10
0 / 65,535 deg
0 / 65,535 mm

RW 16-bit

Integer

Max Speed

61

Max Speed Enable
Maximum Speed Enable
Enable Safe Maximum Speed Monitoring.

Default:
Options:

0 = “Disable”
0 = “Disable”
1 = “Enable”

RW 8-bit

Integer

62

Safe Max Speed
Safe Maximum Speed
Defines the maximum speed limit that will be tolerated if Safe Maximum Speed
monitoring is enabled.

Units:

Default:
Min/Max:

RPM
mm/s
0
0 / 65,535 RPM
0 / 65,535 mm/s

RW 16-bit

Integer

63

Max Spd Stop Typ
Maximum Speed Stop Type
Defines the safe stop type that will be initiated in the event of a SMS Speed Fault.
“Torque Off” (0) – Safe Torque Off With Standstill Checking
“Safe Stp Typ” (1) – Safe Torque Off Without Standstill Checking

Default:
Options:

0 = “Torque Off”
0 = “Torque Off”
1 = “Safe Stp Typ”

RW 8-bit

Integer

64

Max Accel Enable
Maximum Acceleration Enable
Enable Safe Maximum Acceleration Monitoring.

Default:
Options:

0 = “Disable”
0 = “Disable”
1 = “Enable”

RW 8-bit

Integer

65

Safe Accel Limit
Safe Acceleration Limit
Defines the Safe Maximum Acceleration Limit, relative to encoder 1, for which the
system is being monitored.
Units are based on rotary or linear configuration defined by P29 [Fbk 1 Units].

Units:

Default:
Min/Max:

Rev/s

2

mm/s

2

0
0 / 65,535 rev/s

2

0 / 65,535 mm/s

2

RW 16-bit

Integer

66

Max Acc Stop Typ
Maximum Acceleration Stop Type
Defines the safe stop type that will be initiated in the event of an Acceleration Fault.
“Torque Off” (0) – Safe Torque Off With Standstill Checking
“Safe Stp Typ” (1) – Safe Torque Off Without Standstill Checking

Default:
Options:

0 = “Torque Off”
0 = “Torque Off”
1 = “Safe Stp Typ”

RW 8-bit

Integer