Speed Monitoring I/O Signals

Safe Stop Input (SS_In)

The SS_In input is intended for connection to an E-Stop device.

The SS_In input must be active to initiate Safe Stop monitoring. If the SS_In
input is being monitored, a transition from ON to OFF (closed to open) is used
to request the configured Safe Stop Type.

In a cascaded configuration, the SS_In inputs of the middle and last drives are
connected to the Safe Stop (SS_Out) output of an upstream safety option.

Safe Limited Speed Input (SLS_In)

The SLS_In input is used to connect to a switch whose OFF state requests Safe
Limited Speed monitoring.

If Safe Limited Speed monitoring is configured, the SLS_In input is monitored
from the time of a successful Safe Stop Reset or Safe Limited Speed Reset, until
the time that the configured Safe Stop Type is initiated or the Safe State is
entered.

If the SLS_In input is being monitored, the OFF state is used to request the Safe
Limited Speed monitoring functionality of the safety option.

In a cascaded configuration, the SLS_In inputs of the middle and last drives are
connected to the Safe Limited Speed (SLS_Out) output of an upstream safety
option.

Door Monitor Input (DM_In)

This input monitors the status of the door to indicate if it is open or closed. The
DM_In input can be connected to a non-guardlocking switch if the door does
not need to be locked. The door status is monitored by the first unit in multi-axis
systems.

The DM_In input is intended for connection to a guardlocking switch when the
safety option is configured as a master device with door monitoring. When the
safety option is configured as a slave in a cascaded system, its DM_In input is
connected to the Door Control output (DC_Out) of the upstream safety option.

Refer to

Door Control Output (DC_Out)

on

page 44

for more information.