Programming chapter 3 – Rockwell Automation 1771-PD PID MODULE (+DU) User Manual

Page 104

Advertising
background image

Programming

Chapter 3

3Ć61

Figure 3.19

Status Monitor Byte

1

0

07

06

05

04

03

02

01

00

0

0

1

ALARM

CONDITION

POWER-UP

LOSS OF

+

POWER

LOSS OF

AN INPUT

SOFT

FAULT

MODE

SMB B03

1 = in powerĆup mode

SMB B02

Set if an input has been lost. This could be

Loss of Analog Input 1 W61 B07

Loss of Tieback Input 1 W61 B06

Loss of Analog Input 2 W68 B07

Loss of Tieback Input 2 W68 B06

SMB B01

Set for loss of +15V dc power (same status as W58 B11)

SMB B00

Set in soft fault mode (same status as W58 B10)

SMB B07

Set to 0

SMB B06

Set to 0

SMB B05

Set to 1

SMB B04

Set when any of the following bits are set in

the status word for Loop 1 W61 or Loop 2 (W68).

B15, E < EMN

B14, E > EMP

B10, V

I

> V

I

MAX

B05, in manual mode

B03, V

P

> 4095

B02, V

D

>V

D

MAX

B01, V < VMIN

B00, V > VMAX

Also set when the dynamic block error bit W58

B15 = 1 or when the loop block error bit W58 B14 = 1