Chapter 5

5Ć8

Control bits can be set by loading hex values into control words. Hex
values which must be set as part of the calibration procedures are listed in
Table 5.B and described in a. through d. as follows:

a.

Calibration bit B13 in word W01 must be set at module power
up to place the PID module in calibration mode. Load C800
hex into word W01.

b.

The input to be calibrated in sections titled Voltage Reference
and Current Inputs through section titled Output Amplifier,
Voltage Adjustments is selected by loading the corresponding
hex value into word W02.

c.

The full-scale SET OUT value of OFFF hex must be loaded into
word W05 for loop 1 (1 word W12 for loop 2) for calibration
procedures in sections titled Current Inputs and Tieback Current
Inputs.

d.

The set output bit B01 for loop 1 (B02 for loop 2) must be set in
word W01 to download the SET OUT value of OFFF hex to the
PID module in calibration procedures in sections titled Current
Inputs and Tieback Current Inputs.

Table 5.B

Calibration Values

Description

Procedure

Word

Hex Value

Calibration bit

Power up

W01

C800

Input select

analog input 1

tieback input 1

analog input 2

tieback input 2

5.4.2

and

5.4.5

thru

5.4.7

W02

W02

W02

W02

AĆB

ISA

0000

0001

4000

4001

8000

8001

C000

C001

SET OUT value

loop 1

loop 2

5.4.5

and

5.4.6

W05

W12

OFFF

OFFF

Set Output bit

loop 1

loop2

5.4.5

and

5.4.6

W01

W01

C802

C804