Rockwell Automation 1771-PD PID MODULE (+DU) User Manual

Page 230

Advertising
background image

Summary Word and Bit Tables

Appendix D

DĆ9

Table D.D

Control Word A W18(W38)

Bit

Title

Status

B17

Block identifier

0 in W18
1 in W38

B16

Block identifier

0 in W38
1 in W18

B15

Source of PV

0=analog hardware input
1=PC processor, W09(W16)

B14

Square root of PV

0=reset
1=enable

B13

Error polarity

0=SP-PV direct acting
1=PV-SP reverse acting

B12

Error limit

0=rest
1=enable EMN in W21(W41) and EMP in W22(W42)

B11

Dead band

0=reset
1=enable DB in W23(W43)

B10

Maximum integral term limit

0=reset
1=enables VIMAX in W26(W46)

B07,B06

Proportional term error

00=E
01=2/3E + 1/3E@

B05,B04

Integral term error

10=1/3E + 2/3E@
11=E@

B03

Derivative term error

0=error
1=PV

B02

Maximum derivative term limit 0=reset

1=enables VDMAX in word W27(W47)

B01

Hold PID calculation

0=reset
1=hold VPID last value

B00

Hold bias

0=reset
1=hold BIAS last value