Programming chapter 3 – Rockwell Automation 1771-PD PID MODULE (+DU) User Manual

Page 81

Advertising
background image

Programming

Chapter 3

3Ć38

W61(W68) Loop Status. This word indicates various alarm conditions
for the corresponding loop and contains sign information for certain status
block words. Bits 17 through 00 of the loop status word are defined
below and summarized in Figure 3.12 for loop 1 word W61 and loop 2
word W68.

Figure 3.10

Loop Time/Diagnostic Word W60

a) Loop time

Selected by W01 B07=0.

XYZ = Loop time in milliseconds

b) Diagnostics

Selected by W01 B07=1

AB, CD = Diagnostic error codes

X

Y

Z

1 0 0 0

17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

B

C

D

A

Upper byte two digit

BCD code indicates

which word in the

dynamic block is in error.

Lower byte two digit

BCD code indicates which

word in the loop 1 or loop

2 block is in error

11113

Figure 3.11

Loop Update Time

100 msec

PID Algorithm Internal Housekeeping

Nominal Loop Update Time 100 msec

0

Read

Input

1

Read

Input

2

Calc

Output

1

Calc

Output

2

Set

Output

1

Set

Output

2

11114