General

Auto/Manual

Manual

11104

Manual Control

Station

Switch

Request

Input

The PID module is designed for use with commercially available manual
control stations, one per loop. The station is connected between the
analog output and the controlled element of the process. The station
provides manual override control and automatic backup to the PID
module. Manual control stations can be used for start-ups, on-line process
adjustments, and routine maintenance. The station can be used in either
of two ways, manual override control or module back-up.

Manual Override Control

An operator can override automatic control by switching to manual
control and adjusting the output at the manual control station. When the
manual control station is switched to manual mode, a connection is closed
between the MANUAL MODE terminal (referenced to +15V dc) and the
MODULE COMMON terminal on the PID module (Figure 2.8). This

Manual Control Station Interface