Programming chapter 3 – Rockwell Automation 1771-PD PID MODULE (+DU) User Manual

Page 63

Advertising
background image

Programming

Chapter 3

3Ć20

Figure 3.6

Control Word A, Loop 1 W18 and Loop 2 W38

Loop 1

1

0

0

1

PC

LIMIT

PV

VD MAX

LIMIT

HOLD

PID1

HOLD

BIAS1

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

1

0

1

0

W18

Loop 2

W38

PV1

PID

PC

PV2

PID

PV1

PV2

PV-SP

ERROR1

SP-PV

PV-SP

ERROR2

SP-PV

ERROR1

LIMIT

ERROR2

DEAD BAND

DEAD BAND

V1 MAX

LIMIT

V1 MAX

LIMIT

PROPORTIONAL

ERROR

FUNCTION

PROPORTIONAL

ERROR

FUNCTION

INTEGRAL

ERROR

FUNCTION

INTEGRAL

ERROR

FUNCTION

DERIV. ERR.

Error

PV

DERIV. ERR.

Error

VD MAX

LIMIT

HOLD

PID2

HOLD

BIAS2

Note: If you change a loop 1 or loop 2

parameter, you must initiate a load/enter sequence

W18(W38) B07,06

Proportional Error Function, E

P

0 0=Error

0 1=2/3 (Error) + 1/3 (Error)

2

1 0=1/3 (Error) + 2/3 (Error)

2

1 1= (Error)

2

W18(W38) B05,04

Integral Error Function, E

I

0 0=Error

0 1=2/3 (Error) + 1/3 (Error)

2

1 0=1/3 (Error) + 2/3 (Error)

2

1 1= (Error)

2

W18(W38) B03

Derivative Error, E

D

1=PV

0=Error

W18(W38) B02

1=Use derivative term limiting W27(W47)

0=No

limiting

W18(W38) B01

1=Hold last V

PID

value

0=Normal V

PID

calculations

W18(W38) B00

1=Hold last BIAS value

0=Normal BIAS calculations

W18 B17

Must be set to 0: W38 B17 must be set to 1

W18 B16

Must be set to 1: W38 B16 must be set to 0

W18(W38) B15

1=PV from PC Processor W09(W16)

0=PV from hardware analog input

W18(W36) B14

1=Perform square root of PV

0=No square root

W18(W38) B13

1=Error=(PVĆSP) reverse acting

0=Error=(SPĆPV) direct acting

W18(W38) B12

1=Use error limiting W21, W22 (W41, W42)

0=No limiting

W18(W38) B11

1=Use error dead band W23 (W43)

0=No dead band

W18(W38) B10

1=Use integral term limiting W26 (W46)

0=No limiting