Chapter

5

5Ć1

Calibration

The PID module is calibrated before it leaves the factory. The calibration
of the module should be checked yearly. It can be returned to
Allen-Bradley Systems Division for factory calibration. Revision B and
later models can be calibrated using the procedures described in this
chapter.

The following test equipment and parts should be available. Some of this
equipment can be borrowed from the system installation or an
independent test station can be used.

DC Voltage Standard

+10V, 0.1mV resolution

Fluke 342A, or equivalent

Digital Voltmeter

5 1/2 digit, 0.01% accuracy

Keithly 191, Fluke 8300A, or

equivalent

Precision Resistor

AllenĆBradley Systems Division

250 ohms +0.02% 1/4 watt

PN 610996Ć01

Resistor

1000 ohms +l% watt

numerous sources

Industrial Terminal

AllenĆBradley system terminal or

spare, compatible with test PC.

Programmable Controller

System PC or space

Analog Power Supply

AllenĆBradley Power Supply (cat.

no. 1770ĆP1) +15V dc, Ć15V dc,

system supply or spare

Chassis Power Supply

AllenĆBradley (cat. no. 1771ĆP2)

system supply or spare

I/O Chassis

AllenĆBradley (cat. no. 1771ĆA1,ĆA2

or ĆA4) system chassis or system

spare

Extender Board

AllenĆBradley (cat. no. 1771ĆEX)

Field Wiring Arm

AllenĆBradley (cat. no. 1771ĆWF)

system spare

Alignment Tool

pottweeker"

Newark Electronic PN 35F616 or TV

duplex Aligner with plastic shaft, or

equivalent

General

Test Equipment