Aseembly and Installation

Chapter 2

2Ć13

Figure 2.4

Terminal Identification and Connections

Terminal Identification

Cat. No. 1771-PDC

Terminal

Function

18

Input 1 (+ Lead)

17

Input 1 (- Lead)

16

Input 2 (+ Lead)

15

Input 2 (- Lead)

14

Tieback Input 1

13

Tieback Input 2

12

Analog Output 1

11

Module Common

10

Analog Output 2

9

+15V DC

8

15V DC Common

7

-15V DC

6

Manual Mode 1

5

Manual Mode 2

4

Manual Request

3

OPT. +5V DC Common

2

Optional +5V DC

1

Not Used

+-

Process Variable 1

Process Variable 2
Tieback Input 1

Process Variable 2

Process Variable 2

Tieback Input 2

Control Element 1

Module Common

Control Element 2

Required +15V DC Power Supply

(cat. no. 1770-P1, 1778-P2, or equivalent)

Optional +5V DC Power Supply

(cat. no. 1771-P2 or equivalent)

The tieback inputs can be used to track manual control station output to provide bumpless

transfer, or can be used as feedforward inputs.
Module common signal level can be selected to either

15V DC COMMON (system

common) for standard compliance, or -15V DC for additional compliance depending

on the application.
When the manual control station is in manual, the station switches these line to the

MODULE COMMON terminal.
When a request for manual is made from the PID module or when this relay contact output

is used for alarm annunciation, the line is switched to the module common signal level for

50 msec. For hardware failure or loss of analog power ( 15V DC), this relay output is held

at module common until the fault is corrected.
Programming plugs must be positioned for optional +5V DC supply.

+-

+-