Application Example 2, Periodic Block

Transfer

Appendix C

CĆ26

Table C.C

Recommended Output Annunciators

DESCRIPTION

FUNCTION

READ BLOCK TRANSFER

WATCHDOG Indicator

Program Address

012/02

This indicator will illuminate if a read block transfer does not occur within a

predetermined time. The time is determined by the preset value selected for the

timer instruction 043

8

in rung 15 and is userĆselectable. If a read block transfer is

not successfully executed withint the preset time, timer 043

8

will timeĆout and

energize indicator 012/02.

LOAD/ENTER

FAILURE Indicator

Program Address

012/01

This indicator will illuminate in the event of an unsuccessful load/enter sequence.

During program execution, this indicator will normally be off. When a load/enter

sequence is begun, it will illuminate and will remain on until the sequence is

completed (approximately 1 second). If the indicator remains on, then the

load/enter sequence failed. (rung 15).

MANUAL MODE

Indicator

Program Address

012/04

This indicator will illuminiate when the maual control station (if used) is in the

manual mode.

STATUS MONITOR

BYTE ERROR

Indicator

Program Address

012/05

This indicator will show that an alarm condition exists at the module. During

program execution, this indicator will normally be off. If will illuinate when a

condition exists at the module which causes a bit in the status monitor byte to go

high. It will remain on until the error condition is corrected.

NOTE: When this indicator is on, the program will be executing continuou s

load/enter sequences which will allow the source of error be read in the diagnostic

& status words.

Data must be written to the module to correct the problem. Because the program is

executing continuous load/enter sequences, the LOAD/ENTER FAILURE indicator

will be flashing on and off. This condition will occur for any error, read and write

block transfers can be exectued. However no load/enter sequence will be

performed until the soft fault reset bit is set at the module returning the module to

the normal operating mode.

Program for PLCĆ3 Processor

The PLC-3 program for periodic block transfer is presented in Figure 3.7.
Worksheets for the Dynamic Block (Figure C.4figure C.4) and Loop
Blocks (Figure C.5 and NO TAG) also apply to the PLC-3 program. File
storage addresses are listed in Table C.D.