Programming

Chapter 3

3Ć42

Figure 3.12

Loop Status Word, Loop 1 W61 and Loop 2 W68

Loop 1

1

0

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

1

0

W61

Loop 2

W68

NEG.

ERROR1

POS.

NEG.

ERROR2

POS.

NEG.

SCALED PV

POS.

NEG.
POS.

E<EMN1

E<EMN2

E>EMP1

E>EMP2

NEG.

FFV1

POS.

NEG.

FFV2

POS.

LOAD/

ENTER

COMPLETE

0

V > V

MAX

I

I

V > V

MAX

I

I

LOSS OF

ANALOG

INPUT 1

LOSS OF

ANALOG

INPUT 2

LOSS OF

TIEBACK

INPUT 1

LOSS OF

TIEBACK

INPUT 2

MANUAL

MODE

MANUAL

MODE

POWER-UP

COMPLETE

0

V >4095

P

V >4095

P

V > V

MAX

D

D

V > V

MAX

D

D

V<VMIN

V<VMIN

V>VMAX

V>VMAX

W61(W68) B07

1=Loss of analog input

W61(W68) B06

1=Loss of tieback input

W61(W68) B05

1=Auto/manual station in the manual

mode

0=Loop is in the automatic mode under

PID module control

W61(W68) B04

1=PowerĆup sequence is complete, in

W61 only

0=In powerĆup mode; module is

unprogrammed

W61(W68) B03

1=Proportional term > 4095

W61(W68) B02

1=Derivative term > V

D

MAX W27(W47)

W61(W68) B01

1=Algorithm output < VMIN W28(W48)

W61(W68) B00

1=Algorithm output > VMAX W29(W49)

W61(W68) B17

1=ERROR W62(W68) has negative value

0=ERROR has positive value

W61(W68) B16

1=Scaled PV W65(W72) has negative value

0= positive value

W61(W68) B15

1=Error < EMN W21(W41)

W61(W68) B14

1=Error > EMP W22(W42)

W61(W68) B13

1=FFV has a negative value

0=FFV has a positive value

W61 B12

1=Load/enter sequence is complete, in W61

only.

W61(W68) B11

1=Error is within the dead band (W23)

0=Error is outside the dead band

W61(W68) B10

1=Integral term > V

I

MAX W26(W46)

11115

SCALED PV

WITHIN

EROR

DEAD BAND
OUTSIDE

IN PROCESS

AUTOMATIC

AUTOMATIC

WITHIN

EROR

DEAD BAND
OUTSIDE