Application Example 2, Periodic Block

Transfer

Appendix C

CĆ18

Bit 11 = 1

Dead band is set to 15 in word W23.

Bit 10 = 1

Integral output is limited to 4000 in
wordW26.

Bits 07,06 = 0

Proportional error is not modified.

Bits 05, 04 = 0

Integral error is not modified.

Bit 03 = 0

Derivative error is not modified.

Bit 02 = 0

Derivative output is not limited.

Bit 01 = 0

PID output is not held.

Bit 00 = 0

Bias is not held.

Loop 1 Control Word B W 19

Bit 17 = 0

Bias is added to the output.

Bit 16 = 1

Output is limited to 4050 in word W28 for
loop 1.

Bit 15 = 1

Soft fault response is to continue PID
control.

Bit 14 = 0

Soft fault response is to continue PID
control.

Bit 13 = 0

Soft fault response is to continue PID
control.

Bit 12 - 0

Digital filter time x1.

Bits 11,10 = 0

Lead/lag time multiplier is x1.

Bit 07 = 0

Set point sign is positive.

Bits 05,04 = 0

K

P

multiplier is x1.

Bits 03,02 = 0

K

I

multiplier is x1.

Bits 01,00 = 0

K

D

multiplier is x1.

Loop 1 Expanded Control Word W30
Bit 17 = 1

Process variable is scaled.

Bit 16 = 1

Set point is scaled.

Bit 15 = 1

Error is scaled.

Bits 14 thru 00=0

None of these features are used.

Loop 2 Control Word A W38

Bit 17 = 1

Block identifier must be 1.

Bit 16 - 0

Block identifier must be 0.

Bit 15 = 0

Source of the process variable input is the
analog input.

Bit 14 = 1

Square root modifies the analog input.

Bit 13 = 0

Error is positive (SP-PV).

Bit 12 = 0

Error limiting is not used.

Bit 11 = 1

Dead band is set to 20 in word W43.