Calibration procedures – Rockwell Automation 1771-PD PID MODULE (+DU) User Manual

Page 144

Advertising
background image

Chapter 5

5Ć9

NOTE: When the dynamic block containing the calibration bit is first
transferred after power up, the module automatically enters calibration
mode. Place the module in calibration mode as follows:

set W01 B13 by loading C800 hex into word W01
cycle backplane power to the PID module

Module calibration consists of the following seven procedures.

1.

Voltage reference

2.

A/D offset error and gain error compensation

3.

isolation amplifiers

4.

output amplifiers, current mode

5.

current inputs, +4 to +20mA

6.

tieback inputs, +4 to +20mA

7.

output amplifiers, voltage mode

Procedures 3 through 7 require the calibration of loop 1 followed by the
calibration of loop 2 before starting the next procedure.

Calibration adjustments should be set to the exact values stated in the text
except where a tolerance is given. Calibration readings should be made to
+0.0002V dc.

Field wiring arm terminals are referred to in the calibration procedures as
TERMINAL followed by a number.

Voltage Reference

Adjust the module’s precision voltage reference to -10.0000V dc using the
following procedure. The programming plugs should be set for voltage
mode as described in section titled Installation

1.

Connect the digital voltmeter as follows:

Calibration Procedures