Assembly and Installation

Chapter 2

2Ć2

Table 2.A

Indicator Diagnostics

Indicator

State

Condition

FAULT

(red)

OFF

ON

Normal operation.

Hardware fault. Analog outputs are held at either last

state, minimum or maximum value as determined by the

userĆselected programming plugs. If this indicator is on,

the other indicators are not valid

RUN

(green)

ON

Flashing

OFF

Toggle

Normal operation

PID module is initially powered (unprogrammed and is

waiting for data from the PC processor.

PID module is not in the normal run mode.

Analog power (+15V dc) is lost when STAND ALONE

and RUN indicators are alternately toggling on and off.

STAND

ALONE

(yellow)

OFF

Flashing

Toggle

ON

Normal operation

The module is in soft mode and is controlling PID loops

independently. It is not communicating with an active PC

Processor.

NOTE: Disconnecting the field wiring arm will interrupt

PID control.

Analog power (+15V dc) is lost when STAND ALONE

and RUN indicators are alternately toggling on and off.

A programming error is causing a block transfer

communication error.

NOTE: All indicators are off when in calibration mode.

In order to accommodate a wide variety of applications, a number of
programming (jumper) plugs must be correctly positioned inside the PID
module. The following functions are user-selectable using the
programming plugs:

output range: +4 to +20mA or +1 to +5V dc
input range: +4 to +20mA or +1 to +5V dc
tieback input range: +4 to +20mA or +1 to +5V dc, if used current
output compliance: standard or additional hard fault output: hold last
value or max/min value output for loss of +5V dc: max or min value
+5V dc source: backplane or external

Internal Selections