Programming

Chapter 3

3Ć64

Transfer 8 - The write block transfer must have the enter bit W01 B03 set
to 1. This bit must be set during the initial power-up sequence.

Transfer 9 - The read block transfer will have ready bit W58 B12 reset to
0 and will have the load/enter complete bit W61 B12 and the power-up
complete bit W61 B04 set to 1. This indicates that the PID module has
been programmed and that no errors were detected in the dynamic block
or loop blocks.

After the power-up load/enter sequence, the PID module automatically
sets itself for the next transfer of the dynamic block. Program logic can
immediately initiate the dynamic/status toggle sequence, or it can halt
communication until prompted by a timer and/or SMB error bit.

Table 3.L

Load/Enter Bits

Bit Name

Bit Number

load

enter

W01 B06

W01 B03

powerĆup

ready

W58 B13

W58 B12

load/enter complete

powerĆup complete

W61 B12

W61 B04