Troubleshooting

Chapter 4

4Ć2

Table 4.A

LED Troubleshooting Guide

Indication

Description

Probable Cause

Recommended Action

Normal Condition

Module is programmed and is

executing normal control

FAULT

F RUN

STANDALONE

Module is unĆprogrammed

OnĆboard RAM has been cleared

due to one of the following

conditions:

A) +5V DC power to digital

circuitry has been interrupted,

then restored to module.

B)Module has been powered and

is waiting for the initial load/enter

sequence to be completed without

error.

A)Initiate load/enter sequence to

reĆload RAM and to clear the

condition.

B)Check word W60 (diagnostic

word) in order to determine which

words are in error.

FAULT

RUN

F STANDALONE

Module is in standalone mode in

response to a soft fault.

A condition exists (or did exist)

which caused the I/O to reset.

A)Processor is in program or test

mode.

B)I/O fault has interrupted

processorĆtoĆmodule

communication.

C)PC processor faulted.

W01 Bit B10 must be energized in

order to reset this condition.

A)Switch processor to run mode.

B)Check adapters, power

supplies, communication cables

and correct the condition.

C)Refer to appropriate PC

processor troubleshooting guide

and correct the condition.

FAULT

X RUN

X STANDALONE

Hardware fault in module

A)Module hardware faulted.

A)Cycle +5v DC digital power to

module to clear the fault. If fault

condition persists, replace PID

module.

FAULT

T RUN

T STANDALONE

Indicates loss of +15v DC power

to analog circuitry

A)Wiring error.

B)+15V DC supply is out of spec

or failed.

A) Check all wiring from +15V DC

supply to field wiring arm.

B)Adjust supply or replace it.

FAULT

RUN

STANDALONE

Indicates a block transfer

communication error

A)Block transfer rungs are

incorrectly programmed.

B)Illegal values are in words W03,

W04 or W11.

A)Correct block transfer rungs

B)Insert valid addresses.