Rockwell Automation 1771-PD PID MODULE (+DU) User Manual

Page 135

Advertising
background image

Troubleshooting

Chapter 4

4Ć3

Table 4.B

Program Troubelshooting Guide

Indication

Probable Cause

Corrective Action

Incorrect analog input, tieback input, PV input Programming plugs for conditioning the inputs

are selected incorrectly.

BCD or binary format is chosen incorrectly

Transmitter is misĆcalibrated.

ReĆcheck programming plug selection.

See section titled Internal Selections.

ReĆcheck W01 B12, B11 for BCD or binary

format.

ReĆcheck range and span of transmitter.

Incorrect analog output

As above

Actuator is miscalibrated.

As above

ReĆcheck actuator.

Loss of PV input bit is set

PV from analog input is not being received.

PV from PC processor is not being received.

(The loss of PV input is reported if no signal is

present).

Check signal wiring, module and transmitter

power supplies and input conditioning.

Jumper PV (+LEAD) to +15V DC power

connection. (Loss of pV is reported whether

or not the PC processor is downloading the

analog input).

Block transfer does not occur

Ladder diagram program contains an error.

Check that the block transfer instruction

module address matches the PID module's

location in the I/O rack.

Check preĆconditioning of block transfer

rungs.

Verify that the program is similar to the

example program in the appendix.

Check bits B17 and B16 in the first word of

each write block transfer to ensure proper

settings for dynamic, loop 1, and loop 2

blocks. Check block start address words for

correspondence to data table file locations.