5Ć2

Potentiometer Sealant

Organic Products Torque Seal" P.O.

Box 428, Irving, Texas 75060, or

equivalent

Jumper Clips

EĆZ Mini Hook Jumper 204Ć6w

EĆZ Mini Hook

P. O. Box 450

Arcadia, CA 91006 or equivalent

Disassemble the module by removing the left and right cover plates. The
left-hand board is the digital board. The right hand board under the cover
plate with the terminal identification label is the analog board. Be careful
not to bend the three stake pins when separating the boards.

Extender Board and Jumper Clips

The analog and digital boards must be inserted in an I/O chassis during
calibration so that data can be transferred between PC processor and
module.

The analog board must be connected to the extender board to allow access
to the test points and programming plugs.

Jumper clips or the equivalent must be used to jumper the pair of test pins
on the digital board. The test pins are located at the top of the digital
board near the center between IC numbers 4 and 5, Figure 5.1.

Figure 5.1

Jumper Pin Location (Digital Board)

*

*

Diagnostic

Indicators

E10

No

Plug

E1

Jumper

Test

Pins

Backplane Connector

No

Plug

11138

*Factory Configured Plug