Application Example 1, Continuous Block
Transfer
Appendix B
BĆ11
Table B.B
Functional Bit/Word Descriptions
PROGRAM
ADDRESS
MODULE ADDRESS [1]
FUNCTION
257/01
W01
B01
When set, allows a programmed value to be
downloaded to analog output 1.
275/03
W01
B03
Enter bit
257/06
W01
B06
Load bit
350/12
W58
B12
Ready bit
353/04
W61
B04
PowerĆup bit
353/05
W61
B05
Set when manual control station is in the
manual mode.
353/07
W61
B07
Set when analog input 1 has gone below
minimum.
353/12
W61
B12
Load/enter complete bit
263
8
W05
Analog output 1 download from the PC
processor.
264
8
W06
Loop 1 setpoint
351
8
W59
Contains data table location of the next data
block required by the module.
[1] W01 master control word (dynamic block)
W05 word for set analog output 1 (dynamic block)
W06 set point word (dynamic block)
W58 alarm word (status block)
W59 word for next block start address (status block)