Chapter 5

5Ć7

Display of Hex Value

During the calibration procedure, hex values transferred to and from the
PID module can be displayed by using the industrial terminal in data
monitor mode. With the processor in program mode and the cursor on the
file-to-file move instruction, press (DISPLAY) (1). The block files will
be displayed in hex notation starting with word W01 in position 001.

The status words which must be monitored during calibration have the
same number as the file positions. Disregarding the prefix W, the
following status words can be monitored at the positions stated in
Table 5.A.

These words can be displayed by pressing the key sequence
(DISPLAY)(0)(6)(4). Word 064 will be displayed at the top of the
industrial terminal screen.

Table 5.A

Monitor Words

Word

Title

W64

W66

W71

W73

Analog input 1

Tieback input 1

Analog input 2

Tieback input 2

Setting Word Values

When using the industrial terminal in the data monitor mode, the word
intensified by the field cursor is duplicated in the command buffer at the
bottom of the screen. Enter word values as follows using on-line data
change. With the processor in run/program mode and the ladder diagram
displayed, cursor to the file-to-file move instruction. Press the key
sequence (SEARCH)(5)(1)(DISPLAY)(1). The block files will be
displayed starting with position 001. Place the field cursor on the data of
a word using the (SHIFT)(>), (SHIFT)(<),(^) and/or (v) keys as needed.
Enter or change data through the command buffer using the alphanumeric,
(>) and (<) keys as needed. After the desired value has been entered in
the command buffer, press the (INSERT) key to load this value into the
PC processor memory. The value will be block transferred to the PID
module immediately. The on-line entry of data can be terminated at any
time by pressing (CANCEL COMMAND) twice.