Rockwell Automation 1771-PD PID MODULE (+DU) User Manual

Page 234

Advertising
background image

Summary Word and Bit Tables

Appendix D

DĆ13

Table D.I

Loop Status Word W61(W68)

Bit. No.

Title

Status

B17

Sign of loop error

0=ERROR in W62(W69) is positive.
1=negative sign

B16

Sign of scaled PV

0=PV in W65(W72) is positive.
1=negative sign

B15

ERROR<EMN

0=normal for ERROR in W62(W69)
1=undershoots EMN in W21(W41)

B14

ERROR>EMP

0=normal for ERROR in W62(W69)
1=exceeds EMP in W22(W42)

B13

Sign of FFV

0=FFV in W67(W74) is positive.
1=negative sign

B12

Load/enter complete

0=reset by dynamic block transfer
1=LE sequence completed

B11

ERROR within dead band

0=ERROR is W62(W69) exceeds DB
1=ERROR is within DB W23(W43)

B10

VI\VIMAX

0=normal for ERROR in W62(W69)
1=VI exceeds VIMAX in W26(W46)

B07

Loss of analog input

0=input present in W64(W71)
1=input lost

B06

Loss of tieback input

0=input present in W66(W73)
1=input lost

B05

Manual mode

0=PID control
1=manual mode

B04

Power-up complete

0=reset at start of LE power-up
1=power-up LE sequence completed

B03

VP\4095

0=normal for VP
1=VP exceeds 4095.

B02

VD VDMAX

O=normal for VD

1=VD exceeds VDMAX in W27(W47).

B01

V \ VMIN

0=normal for V
1=V undershoots VMIN in W28(W48).

B00

V \ VMAX

0=normal for V
1=V exceeds VMAX in W29(W49).