Rockwell Automation 1771-PD PID MODULE (+DU) User Manual
Page 234

Summary Word and Bit Tables
Appendix D
DĆ13
Table D.I
Loop Status Word W61(W68)
Bit. No.
Title
Status
B17
Sign of loop error
0=ERROR in W62(W69) is positive.
1=negative sign
B16
Sign of scaled PV
0=PV in W65(W72) is positive.
1=negative sign
B15
ERROR<EMN
0=normal for ERROR in W62(W69)
1=undershoots EMN in W21(W41)
B14
ERROR>EMP
0=normal for ERROR in W62(W69)
1=exceeds EMP in W22(W42)
B13
Sign of FFV
0=FFV in W67(W74) is positive.
1=negative sign
B12
Load/enter complete
0=reset by dynamic block transfer
1=LE sequence completed
B11
ERROR within dead band
0=ERROR is W62(W69) exceeds DB
1=ERROR is within DB W23(W43)
B10
VI\VIMAX
0=normal for ERROR in W62(W69)
1=VI exceeds VIMAX in W26(W46)
B07
Loss of analog input
0=input present in W64(W71)
1=input lost
B06
Loss of tieback input
0=input present in W66(W73)
1=input lost
B05
Manual mode
0=PID control
1=manual mode
B04
Power-up complete
0=reset at start of LE power-up
1=power-up LE sequence completed
B03
VP\4095
0=normal for VP
1=VP exceeds 4095.
B02
VD VDMAX
O=normal for VD
1=VD exceeds VDMAX in W27(W47).
B01
V \ VMIN
0=normal for V
1=V undershoots VMIN in W28(W48).
B00
V \ VMAX
0=normal for V
1=V exceeds VMAX in W29(W49).