Programming chapter 3 – Rockwell Automation 1771-PD PID MODULE (+DU) User Manual

Page 48

Advertising
background image

Programming

Chapter 3

3Ć5

Figure 3.3

Block File Memory Requirements

1 Standard Loop

1 Expanded Loop

2 Standard Loops

2 Expanded Loops

Dynamic

Block

10 Words

Dynamic

Block

10 Words

Loop 1 Constants

Block

12 Words

Loop 1

Constants

Block

19 Words

Status Block

11 Words

Status Block

11 Words

Dynamic

Block

17 Words

Dynamic

Block

17 Words

Loop 1 Constants

Block

12 Words

Loop 2 Constants

Block

12 Words

Loop 1

Constants

Block

19 Words

Loop 2

Constants

Block

19 Words

Status

Block

18 Words

Status

Block

18 Words

11095

Load/Enter Sequence

The load/enter sequence is used when all PID control parameters
(dynamic block and loop block data) are transferred from the PC
processor to the PID module. The load/enter sequence is required at
power-up and whenever it is necessary to change any of the loop
constants in LP1 or LP2 or selected control bits in the master control
word. (After a load/enter sequence has been completed, dynamic block
data can be changed at any time by a write block transfer). Changes to
loop constants require a load/enter sequence as a safety consideration to
prevent inadvertent changes which could adversely affect the system.