Introduction chapter 1 – Rockwell Automation 1771-PD PID MODULE (+DU) User Manual

Page 9

Advertising
background image

Introduction

Chapter 1

1Ć6

Figure 1.2

System Overview

P

r

o
c
e
s
s

Tieback Input

Analog Output (V)

Man/Auto Status

Manual Request

Analog Input (PV)

Optional
User Supplied
Manual Control Station

X

1771 – P1
Supply

PC Processor
or Adapter

1771 – PD
Module

Block Transfer

15V DC

100mA

+

1770 – P1 supply

+5V DC
1.2A
Optional
Supply

11092

Programming Description

The PID algorithm can be adapted to the particular control application by
selecting desired features. The features and parameter values are chosen
and stored in the PC processor data table. The PC processor transfers to
the PID module data table blocks which contain the feature selections and
parameter values. The module uses the values to establish its operational
characteristics. The PC processor can read the module status by
transferring information from the module into the data table.
Communication between PC processor and PID module is performed by
block transfer programming.

Levels of Fault Tolerance

The module has five levels of fault tolerance.

The first level occurs when the PID module is operating properly but a
loss of communication with the active PC processor occurs. The module
enters a mode of operation defined as soft fault. A soft fault occurs when:

Advertising