Summary Word and Bit Tables

Appendix D

DĆ10

Table D.E

Control Word B W19(W39)

Bit

Title

Status

B17

VPID+/xBias

0=for V=VPID + BIAS
1= for V (VPID X BIAS)/4095

B16

Output Limiting

0=reset
1= Limits output V to V MIN in W28(W48) and to V MAX in W29(W49)

B15,B14,
B13

Soft fault mode selection

000=Output goes to minimum value (+1V DC or +4mA).
001=Output holds last state.
010=Output goes to SET OUT value in W05(W12) if W01
B01(B02) = 1. If = 0, PID control continues.
100=PID control continues or it resumed if output had been set.
111= Output goes to maximum value (5V DC or +20mA).

B12

TA multiplier

0=x1
1=x10

Input time constant TA is stored in W20(W40).

B11

TB multiplier

0=x1
1=x10

Lead time constant TB is stored in W35(W56).

B10

TC multiplier

0=x1

1=x10

Lag time constant TC is stored in W36(W56).

B07

Scaled SP sign

0=+
1=-

Set point is stored in W06(W13).

B06

Scaling word multiplier

0=x1
1=x10

for W06(W13, W31(W51, W32(W52, W62(W69) and

W65(W72) when scaled

B05,B04

Proportional gain

multiplier for W07
(W14)

00=x1
01=divided by 10

B03,B02

Integral gain multiplier
for W24(W44)

10=x10

11=x100

Multiplier codes 00 thru 11 apply to bits B05 thru B00.

B01,B00

Derivative gain multiplier for W25(W45)