Rockwell Automation 1771-PD PID MODULE (+DU) User Manual
Page 233

Summary Word and Bit Tables
Appendix D
DĆ12
Table D.G
Alarm Word W58
Bits
Title
Status
B17,B16
Block identifier
will be 0
B15
Dynamic block error 0=no error
1=programming error
B14
Loop block error
0=no error
1=programming error
B13
Power-up
0=Dynamic block is received.
1=Memory is clear, ready for LE sequence.
B12
Ready
0=normal
1=Load portion of LE sequence is complete, ready for enter portion.
B11
Loss of +15V DC
0=normal
1=loss of +15V DC
B10
Soft fault mode
0=normal mode
1=soft fault mode
B07 thru
B00
Future use
will be 0
Table D.H
Status Monitor Byte
Bit No.
Title
Status
B07,B06
Precondition
0=Byte is valid.
1=invalid byte
B05
Precondition
0=Byte is invalid
1=valid byte
B04
Alarm
0=no alarm condition
1=An alarm condition is reported in loop status word W61(W68).
B03
Power-up
0=Dynamic block is received.
1=Memory is clear, ready for LE sequence. (SMB B03 mirrors the status of W58
B13).
B02
Loss of input
0=Signal is present
1=loss of analog input or tieback input (under most circumstances)
B01
Loss of +15V DC
0=normal
1=loss of +15V DC (SMB B01 mirrors the status of W58 B11).
B00
Soft fault mode
0=normal mode
1=soft fault mode (SMB B00 mirrors the status of W58 B10).