Rockwell Automation 1771-PD PID MODULE (+DU) User Manual

Page 233

Advertising
background image

Summary Word and Bit Tables

Appendix D

DĆ12

Table D.G

Alarm Word W58

Bits

Title

Status

B17,B16

Block identifier

will be 0

B15

Dynamic block error 0=no error

1=programming error

B14

Loop block error

0=no error
1=programming error

B13

Power-up

0=Dynamic block is received.
1=Memory is clear, ready for LE sequence.

B12

Ready

0=normal
1=Load portion of LE sequence is complete, ready for enter portion.

B11

Loss of +15V DC

0=normal
1=loss of +15V DC

B10

Soft fault mode

0=normal mode
1=soft fault mode

B07 thru
B00

Future use

will be 0

Table D.H

Status Monitor Byte

Bit No.

Title

Status

B07,B06

Precondition

0=Byte is valid.
1=invalid byte

B05

Precondition

0=Byte is invalid
1=valid byte

B04

Alarm

0=no alarm condition
1=An alarm condition is reported in loop status word W61(W68).

B03

Power-up

0=Dynamic block is received.
1=Memory is clear, ready for LE sequence. (SMB B03 mirrors the status of W58

B13).
B02

Loss of input

0=Signal is present
1=loss of analog input or tieback input (under most circumstances)

B01

Loss of +15V DC

0=normal
1=loss of +15V DC (SMB B01 mirrors the status of W58 B11).

B00

Soft fault mode

0=normal mode
1=soft fault mode (SMB B00 mirrors the status of W58 B10).