Pr - 0.01] motor and encoder selection, Pr – 0.01] motor and encoder selection -15 – Rockwell Automation 2092-DAx Ultra1500 Host Commands for Serial Communication Reference Manual User Manual

Page 27

Advertising
background image

Publication 2092-RM001A-EN-P — March 2005

Command Reference

2-15

[Pr – 0.01] Motor and Encoder Selection

Operating Mode:

All

Data Size:

4 digits

Digit 0:

Automatic motor identification

Ultraware Name:

Auto Motor Iden

Range: Value

Description

0x0

Disable automatic motor identification

0x1

Enable automatic motor identification

Default: 1

Digit 1:

Single turn absolute

Ultraware Name:

Encoder Backup Battery

Range: Value

Description

0x0

Installed

0x1

Not Installed

Default: 0

Digit 2:

Encoder line break detect

Ultraware Name:

Incremental Feedback Loss

Range: Value

Description

0x0

Monitor encoder feedback loss error
checking

0x1

Ignore encoder feedback loss error checking

Default: 0

Digit 3:

Reserved

Default: 0

Advertising