Group 4 parameters, Pr - 4.00] current scale, Pr - 4.01] positive internal current limit – Rockwell Automation 2092-DAx Ultra1500 Host Commands for Serial Communication Reference Manual User Manual

Page 42: Pr - 4.02] negative internal current limit, Pr - 4.03] positive external current limit, Pr - 4.04] negative external current limit, Group 4 parameters -30

Advertising
background image

Publication 2092-RM001A-EN-P — March 2005

2-30

Command Reference

Group 4 Parameters

[Pr – 4.00] Current Scale

[Pr – 4.01] Positive Internal Current Limit

[Pr – 4.02] Negative Internal Current Limit

[Pr – 4.03] Positive External Current Limit

[Pr – 4.04] Negative External Current Limit

Range:

0 to 1000

Default:

333

Units:

% of rated continuous current/V *10

Operating Mode:

Analog Current Command, Dual Current Command

Ultraware Name:

Current Limits: Positive Internal

Range:

0 to 500

Default:

500

Units:

% of motor rated continuous current

Operating Mode:

All

Ultraware Name:

Current Limits: Negative Internal

Range:

0 to 500

Default:

500

Units:

% of motor rated continuous current

Operating Mode:

All

Ultraware Name:

Current Limits: Positive External

Range:

0 to 500

Default:

100

Units:

% of motor rated continuous current

Operating Mode:

All

Ultraware Name:

Current Limits: Negative External

Range:

0 to 500

Default:

100

Units:

% of motor rated continuous current

Operating Mode:

All