Speed reference limits, Current limit stop, Speed error – Rockwell Automation 20D PowerFlex 700S with Phase I Control Reference Manual User Manual

Page 122

Advertising
background image

122

Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013

Chapter 1

Detail Drive Configuration and Operation

Bit 8 - “Spd Reg En” Indicates that the output of the speed regulator is
enabled and the output is allowed to enter the torque loop.

Speed Reference Limits

At this point the summed speed reference is limited by parameters 30 [Rev Speed
Limit] and 31 [Fwd Speed Limit]. Those limits are set at -2187.5 RPM and
2187.5 RPM default.

Current Limit Stop

When a current limit stop is commanded, [Logic Ctrl State] bit 6 - “CurrLim
Stop” is set. Then a 0 speed reference command is sent into the speed regulator,
bypassing the ramp and speed trimming.

Speed Error

The summed speed reference becomes parameter 301 [Motor Speed Ref ]. Then
the filtered motor speed feedback is subtracted from the motor speed reference to
create a speed error.

0

Autotune

Bypass

19

157

5

8

157

04

Logic Ctrl State

Atune Spd Ref

Logic Ctrl State

(Inrta Tst En)

(J Tst FulSpd)

(Spd Reg En)

1

30

31

Limit

Rev Speed Limit

Fwd Speed Limit

0

1

157

06

0

Logic Ctrl State

(CurrLim Stop)

Advertising