Chapter 1

User Functions

There are several user functions available in the drive for custom control.

Peak Detect

There are two peak detectors that can be used to detect the peak for a parameter
value.

Configuration:

Link parameter 213 [PkDtct1 In Real] or parameter 212 [PkDtct1 In Int]
to the parameter that you wish to detect a peak, depending on the data
type.

To detect positive peak values, turn on parameter 210 [PeakDtct Ctrl In]
bit 2 “Peak1 Sel”. To detect negative peak values, turn off parameter 210
[PeakDtct Ctrl In] bit 2 “Peak1 Sel”.

The peak value is contained in parameter 215 [Peak Detect1 Out].

To reset the output of the peak detector, toggle on and then off parameter
210 [PeakDtct Ctrl In] bit 0 “Peak 1 Set”. The output will match the value
in parameter 214 [PeakDtct1 Preset], which is a default of 0.

To hold the output of the peak detector at the present value, turn on
parameter 210 [PeakDtct Ctrl In] bit 1 “Peak 1 Hold”.

The change bit, parameter 211 [PeakDtct Status] bit 0 “Peak 1 Chng” is set to
“true” for one scan if the peak detect value changes, otherwise the change bit is set
to “False”. The change bit is also set to “False” if the detector is in Set or Hold
mode.

Example:

Link parameter 213 [PkDtct1 In Real] to parameter 300 [Motor Spd
Fdbk].

Verify that parameter 210 [PeakDtct Ctrl In] bit 0 “Peak 1 Set” and bit 1
“Peak 1 Hold” are off.

For parameter 210 [PeakDtct Ctrl In], turn on bit 2 “Peak1 Sel”.

214

212

213

210

2

0

211

1

210

0

210

215

Peak Ctrl Status

(Peak 1 Chng)

PkDtct1 In Real

PeakDtct1 In Int

PeakDtct1 Ctrl In

(Peak 1 Sel)

PeakDtct1 Preset

Peak Detect1 Out

(Peak 1 Set)

PeakDtct1 Ctrl In

(Peak 1 Hold)

218

210

6

1

211

5

210

4

210

219

OR

216

217

Peak Ctrl Status

(Peak 2 Chng)

PkDtct2 In Real

PeakDtct2 In Int

PeakDtct Ctrl In

(Peak 2 Sel)

PeakDtct2 Preset

Peak Detect2 Out

(Peak 2 Set)

PeakDtct2 Ctrl In

(Peak 2 Hold)

OR

Inv

Inv

PeakDtct2 Ctrl In

PeakDtct1 Ctrl In

The change bit , Peak x Chng (where x = 1 or 2), is set TRUE if the peak detect value changes,
otherwise the change bit is set FALSE . Change is also set to FALSE if the detector is in HOLD or SET.