Chapter 1

Detail Drive Configuration and Operation

Settings for parameter 222 [Mtr Fdbk Sel Pri] and parameter
223 [Mtr Fdbk Sel Alt]:

Parameter 224 [TachSwitch Level] sets the detection level for the automatic
speed loss switch over routine. A drop in feedback speed at the percent of rated
speed over a 0.5 ms interval will cause a tach switch from primary to alternate
device. Setting this level lower will make the speed detection more sensitive and
lower the minimum speed at which a speed switch could occur. Setting this level
higher will make the speed switch less sensitive and raise the minimum speed for
speed switch detection.

Parameter 320 [Exception Event1] bits 2 through 5 show the error status of the
corresponding speed feedback device.

Parameter 365 [Fdbk LsCnfg Pri] and parameter 366 [Fdbk LsCnfg Alt] set the
feedback loss configuration for each feedback device. The primary feedback
device should be configured to 1 “Alarm”. The alternate feedback device should
typically be configured to 2 “FltCoastStop”.

Settings for [Fdbk LsCnfg Pri] and [Fdbk LsCnfg Alt]:

Parameter 510 [FVC Mode Config] bit 22 “SrLss RdThru” must be set to “1” if
sensorless operation is selected in [Mtr Fdbk Sel Alt]. In all other cases Parameter
510 bit 22 should be set to “0”.

Speed Feedback Loss Ride Through Operation

Setting up the feedback loss ride through function requires the following steps:

1.

Enter a valid feedback device selection in parameter 222 [Mtr Fdbk Sel
Pri].

2.

Enter a valid feedback device selection in parameter 223 [Mtr Fdbk Sel
Alt].

3.

Setting parameter 365 [Fdbk LsCnfg Pri] to 1 “Alarm.”

4.

Setting parameter 366 [Fdbk LsCnfg Alt] to 2 “FltCoastStop”
(recommended but not necessary).

0 =

Encoder 0

3 =

Reserved

1 =

Encoder 1

4 =

Motor Sim

2 =

Sensorless

5 =

FB Opt Port0

2 =

Encdr0 Loss

3 =

Encdr1 Loss

4 =

FB Opt0 Loss

5 =

FB Opt1 Loss

1 =

Alarm

2 =

FltCoastStop