Unbalanced or ungrounded distribution systems, Unbalanced distribution systems, Ungrounded distribution systems – Rockwell Automation 20D PowerFlex 700S with Phase I Control Reference Manual User Manual

Page 176

Advertising
background image

176

Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013

Chapter 1

Detail Drive Configuration and Operation

Unbalanced or Ungrounded
Distribution Systems

Unbalanced Distribution Systems

This drive is designed to operate on three-phase supply systems whose line
voltages are symmetrical. Surge suppression devices are included to protect the
drive from lightning induced overvoltages between line and ground. Where the
potential exists for abnormally high phase-to-ground voltages (in excess of 125%
of nominal), or where the supply ground is tied to another system or equipment
that could cause the ground potential to vary with operation, suitable isolation is
required for the drive. Where this potential exists, an isolation transformer is
strongly recommended.

Ungrounded Distribution Systems

All drives are equipped with an MOV (Metal Oxide Varistor) that provides
voltage surge protection and phase-to-phase plus phase-to-ground protection
which is designed to meet IEEE 587. The MOV circuit is designed for surge
suppression only (transient line protection), not continuous operation.

With ungrounded distribution systems, the phase-to-ground MOV connection
could become a continuous current path to ground. Energy ratings are listed
below. Exceeding the published phase-to-phase or phase-to-ground energy
ratings may cause physical damage to the MOV.

PowerFlex drives contain protective MOVs and common mode capacitors that
are referenced to ground. To guard against drive damage, these devices should be
disconnected if the drive is installed on an ungrounded distribution system where
the line-to-ground voltages on any phase could exceed 125% of the nominal line-
to-line voltage. Refer to your PowerFlex User Manual, 20D-UM001, for details.

1

2

3

4

Joules (J)

Ground

Three-Phase

AC Input

T

S

R

Joules (J)

Joules (J)

Joules (J)

Device Rating (V AC)

Phase-Phase Total
Phase-Ground Total

240/480 600

280J

320J

360J

410J

240

480/600

160J 320J
220J 380J

240/480 600

280J

300J

360J

370J

Phase-to-Phase MOV Rating

Includes 2 Phase-Phase MOVs

Phase-to-Ground MOV Rating

Includes Phase-Phase & Phase-Ground MOVs

Advertising