Sync Generator

The sync generator can be used to synchronize a parameter and delay it one scan.
This can be used in conjunction with SynchLink (Refer to SynchLink on page

160

for more information).

Configuration:

Parameters 788 [Xsync In 1] and 789 [Xsync Out 1] can be used to
synchronize a Dint parameter.

Parameters 790 [Xsync In2] through 792 [Xsynch Out 2 Dly] can be used
to synchronize a Dint parameter and delay it one scan.

Parameters 793 [Xsync In3] through 795 [Xsynch Out 3 Dly] can be used
to synchronize a floating point parameter and delay it one scan.

Parameter 787 [Xsync Gen Period] sets the scan time of the synch
generator. The following options are available:

The default setting is 1 = “4 msec”.

Test Points

Test points are used to monitor values in the drive for diagnostic information.

[xxxx TP Sel] selects a value to monitor for diagnostics.

[xxxx TP Data] shows the value selected by [xxxx TP Sel].

0 =

2 msec

3 =

16 msec

1 =

4 msec

4 =

32 msec

2 =

8 msec

Latch

Latch

Latch

788

790

793

Sync Generator

787

789

791

792

794

795

317

0.5ms

Xsync In 1

Xsync Out 1

Xsync Out 2

Xsync In 2

Xsync In 3

Xsync Out 2 Dly

Xsync Out 3 Dly

Xsync Out 3

SL System Time

Sync Pulse Generator

0.5ms * 2

(p787)

0.5ms

786

00

Delay

One

Scan

Delay

One

Scan

Xsync Gen Period

Xsync Status
(Sync Pulse)