Accel/decel ramp and s-curve – Rockwell Automation 20D PowerFlex 700S with Phase I Control Reference Manual User Manual

Page 134

Advertising
background image

134

Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013

Chapter 1

Detail Drive Configuration and Operation

Accel/Decel Ramp and S-Curve

The accel/decel ramp generator can be bypassed for certain functions. When
parameter 151 [Logic Command] bit 0 - “SpdRamp Dsbl” is on, the ramp is
bypassed. Otherwise, the reference is ramped according to the rates determined
by parameters 32 [Accel Time] and 33 [Decel Time]. For example, the ramp rate
for acceleration would be [Motor NP RPM]/[Accel Time]. The ramped
reference can be viewed in parameter 42 [Ramped Spd Ref ].

The drive can produce a linear ramp output or an s curve signal. The s curve is
used when [Logic Command] bit 1 - “Spd S Curve En” is on and the ramp is not
bypassed. Parameter 34 [S Curve Time] sets the time that the s curve will be
applied at the beginning and at the end of the ramp. Half of the time specified in
parameter 34 is added to the beginning of the ramp and half to the end of the
ramp (as shown in the example below). The result of the s curve block can be seen
in parameter 43 [S Curve Spd Ref ].

32

33

34

Inv

Logic

1 0
0 1

157

01

&

157

02

151

00

151

01

43

42

Ramp

S Curve

Logic

1 0
0 1

S Curve Spd Ref

Ramped Spd Ref

S Curve Time

Accel Time

Decel Time

Logic Command

(Spd S Crv En)

Logic Ctrl State

(SRef Ramp En)

Logic Ctrl State
(SRef SCrv En)

S Curve Time = 1.0 second

Speed

Time in Seconds

0.5 sec.

Accel Time = 5.0 seconds

Total Ramp Time = 6.0 seconds

0.5 sec.