Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013

Chapter 1

Detail Drive Configuration and Operation

The bits for each parameter are broken down as follows:

Bit 0 - “Digital Input”

Bit 1 - “Adapter 1”

Bit2 - “Adapter 2”

Bit 3 - “Adapter 3”

Bit 4 - Not Used

Bit 5 - “Adapter 5”

Bit 6 - Not Used

Bit 7 - “DriveLogix”

Ownership falls into two categories:

• Exclusive:

Only one adapter at a time can issue the command and only

one bit in the parameter will be high.

• Non Exclusive:

Multiple adapters can simultaneously issue the same

command and multiple bits may be high.

Some ownership must be exclusive; that is, only one Adapter at a time can issue
certain commands and claim ownership of that function. For example, it is not
allowable to have one Adapter command the drive to run in the forward
direction while another Adapter is issuing a command to make the drive run in
reverse. Direction Control, therefore, is exclusive ownership.

Conversely, any number of adapters can simultaneously issue Stop Commands.
Therefore, Stop Ownership is not exclusive.

Example:

The operator presses the Stop button on the Local HIM to stop the

drive. When the operator attempts to restart the drive by pressing the HIM Start
button, the drive does not restart. The operator needs to determine why the drive
will not restart.

The operator first views the Start owner to be certain that the Start button on the
HIM is issuing a command.

When the local Start button is pressed, the display indicates that the command is
coming from the HIM.

Dr

iv

eL

ogix

Not

U

se

d

Ada

pte

r 5

Not

U

se

d

Ada

pte

r 3

Ada

pte

r 2

Ada

pte

r 1

Te

rmin

al Bl

ock

-

Digital Inp

ut

Start Owner

Bit

7 6 5 4 3 2 1 0

Adapter #

0 0 0 0 0 0 1 0

Dr

iv

eL

ogix

Not U

se

d

Ad

ap

te

r 5

Not U

se

d

Ad

ap

te

r 3

Ad

ap

te

r 2

Ad

ap

te

r 1

Te

rmin

al

Bl

ock -

Digital Inp

ut

Start Owner

Bit

7 6 5 4 3 2 1 0

Adapter #

0 0 0 0 0 0 1 0