Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013

Chapter 1

Detail Drive Configuration and Operation

Bit 9 “Edge Time” configures the method of sampling used by the Velocity
Position Loop (VPL). Setting the bit chooses “Edge to Edge” sampling,
while resetting the bit to zero chooses “Simple Difference” sampling.
“Simple Difference” sampling calculates speed by examining the difference
between pulse counts over a fixed sample time. “Edge to Edge” sampling
adjusts the sample time to synchronize with the position count updates
from the daughter card - improving the accuracy of the speed calculation.

Bits 12 “SmplRate bt0” through 15 “SmplRate bt3” configure the sample
interval for measuring speed (see

Table 7

on page

140

). Increasing the

encoder sample interval improves speed measurement near zero speed.
Decreasing allows the speed control regulator to perform with high gains
at high speeds.

Table 7 - Encoder Input Filter Settings

Table 8 - Multiplier and Direction Settings

Bit

3

2

1

0

Encoder Bit Filter Settings

0

0

0

0

Filter disabled

0

0

0

1

100 ns filter

0

0

1

0

200 ns filter

0

0

1

1

300 ns filter

0

1

0

0

400 ns filter

0

1

0

1

500 ns filter

0

1

1

0

600 ns filter

0

1

1

1

700 ns filter

1

0

0

0

800 ns filter (default setting)

1

0

0

1

900 ns filter

1

0

1

0

1000 ns filter

1

0

1

1

1100 ns filter

1

1

0

0

1200 ns filter

1

1

0

1

1300 ns filter

1

1

1

0

1400 ns filter

1

1

1

1

1500 ns filter

Bit

5

4

Mult.

Directions

Comments

0

0

2x

fwd/rev

Counts rise/fall of phase A, phase B only used to find direction

0

1

4x

fwd/rev

Counts rise/fall of both A and B phases (default setting)

1

0

1x

fwd only

Counts rise of phase A. Phase B ignored.

1

1

2X

fwd only

Counts rise of phase A. Phase B ignored.