Chapter 1
Detail Drive Configuration and Operation
Parameter 723 [Dlink OutDataType] needs to be set for the type of data used.
The most common will be Real Data (in other words, Current, Voltage, Torque
are all Real values in the drive). The PowerFlex 700S drive default for this
parameter is all Datalinks set for Integer values. If the check mark is not set then
the datalink is not set for an Integer value (From DriveExecutive).