The following table lists watts loss data for PowerFlex 700S drives running at full
load, full speed, and factory default PWM frequency of 4 kHz.

Table 13 - 480V Watts Loss at Full Load/Speed, 4 kHz

(1)

(1)

Includes HIM

(2)

Information not available at time of publication

Drive ND HP @ 480V AC

Total Watt Loss

0.5

92

1

103

2

117

3

135

5

210

7.5

243

10

271

15

389

20

467

25

519

30

543

40

708

50

(2)

60

(2)

75

(2)

100

(2)

125

(2)

150

(2)

Advertising