Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013

89

Detail Drive Configuration and Operation

Chapter 1

Position Reference Selection

For point to point positioning set parameter 742 [Posit Ref Sel] = 2 “Pt to Pt”.
Parameter 758 [Pt-Pt Posit Ref ] becomes the reference for the position.

Position Reference Scaling

Position reference can be entered in user units by using the EGR scaling.
Parameters 745 [PositRef EGR Mul] and 746 [PositRef EGR Div] are used to
scale the position reference.

Example:

To use degrees of motor revolution for the positioning units, scale as

follows:

With a 1024 encoder on the motor, this translates to 4096 counts per revolution
quadrature position counts.

This scaling translates the position reference of 0…360 degrees to 0…4096
position counts. This will allow you to enter degrees of motor rotation for the
position reference.

0

1

2

749

743

742

Interp Position

Posit Ref Sel

758

Aux PositRef

Pt-Pt Posit Ref

Selected
Position
Reference

Gear Rat

[ N ]
[ D ]

745

746

PositRef EGR Mul

PositRef EGR Div

Accum

744

PositRef EGR Out

Deriv

Δ

Selected position

reference

Geared position

reference

Parameter 745 [PositRef EGR Mul]

=

4096

Parameter 746 [PositRef EGR Div]

=

360