To configure the drive for 3-wire control with a current limit stop:

For parameter 153 [Control Options], set bit 8 “3WireControl” to on (1) and set
bits 3 “2WCurrLimStp” and 9 “2W CoastStop” to off (0).

To control from digital inputs:

1.

Set parameter 839 [DigIn2 Sel] = 9 “Current Limit Stop”

2.

Set parameter 840 [DigIn3 Sel] = 2 “Start”

To control from a communication network:

1.

To perform a current limit stop, toggle bit 8 “CurrLim Stop” in the logic
command word on and then off.

2.

To perform a start, toggle bit 1 “Start” in the logic command word on and
then off.

Note:

In 3-wire mode, all stops commanded from pressing the HIM stop

button are ramp stops.

Configuring the Start and Stop for 2-Wire Control (Maintained Start
and Stop)

To configure the drive for 2-wire control with a ramp stop:

For parameter 153 [Control Options], set bits 3 “2WCurrLimStp”, 8
“3WireControl”, and 9 “2W CoastStop” to off (0).

To control from digital inputs:

Set parameter 839 [DigIn2 Sel] = 3 “Run”

To control from a communication network:

To perform a ramp stop, toggle bit 1 “Start” in the logic command word on
and then off.

To control from the HIM:

Hold down the start button to run and release the start button to perform
a ramp stop.