Chapter 1
Detail Drive Configuration and Operation
Table 12 - Resolver Sample Interval
Parameter 270 [Reslvr0 SpdRatio] specifies the speed ratio for the resolver
option card at port 0. The speed ratio comes from the following formula.
Speed ratio = electrical revolutions / mechanical revolutions = pole count / 2.
Parameter 271 [Reslvr0 Carrier] specifies the resolver carrier frequency for the
resolver option card at port 0.
Parameter 272 [Reslvr0 In Volts] specifies the resolver input voltage for the
resolver option card at port 0.
Parameter 273 [Rslvr0 XfrmRatio] specifies the resolver transform ratio for the
resolver option card at port 0.
Parameter 274 [Reslvr0 CableBal] specifies the resolver cable balance for the
resolver option card at port 0.
Bit
15
14
13
12
Resolver Sample Interval Settings
0
0
0
0
0.5 ms
0
0
0
1
0.5 ms (min. setting)
0
0
1
0
1.0 ms
0
0
1
1
1.5 ms
0
1
0
0
2.0 ms (default setting)
0
1
0
1
2.5 ms
0
1
1
0
3.0 ms
0
1
1
1
3.5 ms
1
0
0
0
4.0 ms
1
0
0
1
4.5 ms
1
0
1
0
5.0 ms
1
0
1
1
5.5 ms
1
1
0
0
6.0 ms (max. setting)
1
1
0
1
6.0 ms
1
1
1
0
6.0 ms
1
1
1
1
6.0 ms