Chapter 1

Detail Drive Configuration and Operation

Table 12 - Resolver Sample Interval

Parameter 270 [Reslvr0 SpdRatio] specifies the speed ratio for the resolver
option card at port 0. The speed ratio comes from the following formula.

Speed ratio = electrical revolutions / mechanical revolutions = pole count / 2.

Parameter 271 [Reslvr0 Carrier] specifies the resolver carrier frequency for the
resolver option card at port 0.

Parameter 272 [Reslvr0 In Volts] specifies the resolver input voltage for the
resolver option card at port 0.

Parameter 273 [Rslvr0 XfrmRatio] specifies the resolver transform ratio for the
resolver option card at port 0.

Parameter 274 [Reslvr0 CableBal] specifies the resolver cable balance for the
resolver option card at port 0.

Bit

15

14

13

12

Resolver Sample Interval Settings

0

0

0

0

0.5 ms

0

0

0

1

0.5 ms (min. setting)

0

0

1

0

1.0 ms

0

0

1

1

1.5 ms

0

1

0

0

2.0 ms (default setting)

0

1

0

1

2.5 ms

0

1

1

0

3.0 ms

0

1

1

1

3.5 ms

1

0

0

0

4.0 ms

1

0

0

1

4.5 ms

1

0

1

0

5.0 ms

1

0

1

1

5.5 ms

1

1

0

0

6.0 ms (max. setting)

1

1

0

1

6.0 ms

1

1

1

0

6.0 ms

1

1

1

1

6.0 ms