Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013

Chapter 1

Detail Drive Configuration and Operation

CE Conformity

Compliance with the Low Voltage (LV) Directive and Electromagnetic
Compatibility (EMC) Directive has been demonstrated using harmonized
European Norm (EN) standards published in the Official Journal of the
European Communities. PowerFlex drives comply with the EN standards listed
below when installed according to the PowerFlex 700S AC Drives Phase I
Control User and Reference Manuals.

CE Declarations of Conformity are available online at:

http://www.rockwellautomation.com/products/certification/

Low Voltage Directive (2006/95/EC)

EN 61800-5-1 Adjustable speed electrical power drive systems - Part 5-1:
Safety requirements – Electrical, thermal and energy.

EMC Directive (2004/108/EC)

EN 61800-3 Adjustable Speed Electrical Power Drive Systems - Part 3:
EMC Product Standard Including Specific Test Methods.

Common Bus Systems

See the Common Bus section in publication

DRIVES-IN001

for detailed

information. For information on the 1336R Regen unit, see Bus Regulation/
Braking
on page

20

.

Communication

See individual adapters sections: ControlNet (20-COMM-C) on page

26

,

DeviceNet (20-COMM-D) on page

36

, and Remote I/O Adapter (20-COMM-

R) on page

106

.

ControlNet (20-COMM-C)

This information serves as a supplement to the PowerFlex ControlNet Adapter
Users Manual, publication

20COMM-UM003

, addressing items specific to the

PowerFlex 700S. Please refer to the User Manual for details on 20-COMM-C
set-up, configuration, I/O messaging, and explicit messaging. This document
does not apply to the DriveLogix communications to the 700S.

Setup Information

Parameters 25 [M-S Input] and 26 [M-S Output] of the 20-COMM-C must be
configured for the Datalinks that are to be used. If changes are made to these
parameters or others, parameter 9 [Reset Module] must be set to reset module for
the change to take effect. Set rotary switches to the correct node address. Node
02 is used for all Datalinks in this example.