High overload – Rockwell Automation 20D PowerFlex 700S with Phase I Control Reference Manual User Manual

Page 74

Advertising
background image

74

Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013

Chapter 1

Detail Drive Configuration and Operation

Figure 24 - Illustration of IL

High Overload

After continuous operation at the rated output current, overload may be 150%
rated output current (IH) for 1 minute as long as it is followed by a period of load
less than the rated current so that the output current over the duty cycle does not
exceed the rated output current (IH).

Example:

If the duty cycle requires 150% rated output current for 1 minute of

every 10 minutes, the remaining 9 minutes must be at approximately 92% rated
current or less to maintain output current less than 100%. If the requirement is 1
minute out of 60 minutes, the remaining 59 minutes must be at approximately
98% rated current or less.

1 minute

9 minutes

1.1 x I

L

Time

Current

I

L