159

Detail Drive Configuration and Operation

Chapter 1

To configure the drive for 2-wire control with a coast stop:

For parameter 153 [Control Options], set bit 9 “2W CoastStop” to on (1) and
set bits 3 “2WCurrLimStp” and 8 “3WireControl” off (0).

To control from digital inputs:

Set parameter 839 [DigIn2 Sel] = 3 “Run”

To control from a communication network:

To perform a coast stop, toggle bit 1 “Start” in the logic command word on
and then off.

To control from the HIM:

Hold down the start button to run and release the start button to perform
a coast stop.

Note:

When P153 [Control Options] bit 9 is on, and bits 3 and 8 are off

all other stop commands become coast stops because of the priority of the
stop types. For example, if you try to command a ramp stop or current
limit stop from a communication network, the drive will still perform a
coast stop.

To configure the drive for 2-wire control with a current limit stop:

For parameter 153 [Control Options], set bits 3 “2WCurrLimStp” to on (1) and
bits 8 “3WireControl” and 9 “2W CoastStop” to off (0).

To control from digital inputs:

Set parameter 839 [DigIn2 Sel] = 3 “Run”

To control from a communication network:

To perform a current limit stop, Toggle bit 1 “Start” in the logic command
word on and then off.

To control from the HIM:

Hold down the start button to run and release the start button to perform
a current limit stop

Note:

When parameter 153 [Control Options] bit 3 is on, and bits 8 and

9 are off the ramp (normal) stop becomes a current limit stop. For
example, if you try to command a ramp stop from a communication
network, the drive will still perform a current limit stop. A coast stop can
still be performed by commanding a coast stop.