Rockwell Automation 20D PowerFlex 700S with Phase I Control Reference Manual User Manual

Page 145

Advertising
background image

Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013

145

Detail Drive Configuration and Operation

Chapter 1

Resolver Feedback Option

Parameter 266 [Reslvr0 Config] is used to configure the resolver feedback
option.

Setting bit 0 “Cable Tune” enables the cable tuning test, resetting the bit to zero
disables the test. This test automatically runs on power up to measure the IR drop
in the resolver cable.

Bit 1 “Reserved” (not used)

Bits 2 “Resolution 0" and bit 3 “Resolution 1" select the resolver resolution
(see

Table 11

).

Setting bit 4 “Energize” energizes the resolver, resetting the bit to zero de-
energizes it.

Bit 5 “Resolver Dir” determines counting direction. If clear, direction is
forward or up. If set, the direction is reverse or down.

Bit 9 “Reserved” (not used)

Bits 10 “Reserved” (not used)

Bits 12…15 “SmplRate bt 0” - “SmplRate bt3” configure the sample
interval for measuring speed (refer to

Table 12

). Increasing the resolver

sample interval improves speed measurement near zero speed. Decreasing
the resolver sample interval allows the speed control regulator to perform
with high gains at high speeds.

Table 11 - Resolution Settings

Bit

3

2

Resolution Setting

0

0

10 bit

0

1

12 bit (default setting)

1

0

14 bit

1

1

16 bit