Detail Drive Configuration and Operation

Example:

Tag names:
Outputs to the Drive - PowerFlex700S_02:O[0] … [9]
Inputs from the Drive - PowerFlex700S_02:I[0] … [10] word [0] reserved

Figure 3

is an example using Bits in the ControlLogix processor to write to the

output bits associated to parameter 158 [Drive Logic Rslt]

PowerFlex700S_02:O[0].0….9 map to parameter 158 [Drive Logic Rslt]

Figure 3 - Using Bits in ControlLogix

Technical Information

To use the 20-COMM-C with the PowerFlex 700S, the 20-COMM-C must be
v1.003 firmware or later.

The Logic Command and Logic Status are 32 bit data, but only the first 16 are
used. The bit definitions of the Logic Command word follow the same pattern as
parameter 158 [Drive Logic Rslt]. The bit definitions of the Logic Status word
follow the same pattern as bits 0-15 of parameter 155 [Logic Status].

Reference and Feedback are 16 bit unsigned integer data. Datalinks are 32 bit
data.

Figure 4

on page

29

shows I/O Image table for a ControlLogix system.

I.Data[0] is reserved.

PF700S_Coast Stop

PF700S_CurrLim_Stop

PF700S_Clear_Fault

PF700S_UniPol_Fwd

PF700S_UniPol_Rev

PF700S_Jog2

PF700S_Jog1

PF700S_Start

PF700S_Normal_Stop

PowerFlex700S_02:0.Data[0].1

PowerFlex700S_02:0.Data[0].0

PowerFlex700S_02:0.Data[0].8

PowerFlex700S_02:0.Data[0].7

PowerFlex700S_02:0.Data[0].5

PowerFlex700S_02:0.Data[0].3

PowerFlex700S_02:0.Data[0].2

PowerFlex700S_02:0.Data[0].9

PowerFlex700S_02:0.Data[0].4