Chapter 1

Detail Drive Configuration and Operation

Sensorless

Sensorless mode is used when zero speed or more than a 120:1 speed range is not
required.

Parameter 548 [Est Speed Fdbk] contains the estimated motor speed, used when
sensorless mode is selected. The estimated speed feedback is based on voltage
feedback from the motor. [Est Speed Fdbk] is scaled so that a value of 4096
equals parameter 4 [Motor NP RPM].

The estimated speed feedback is converted to RPM, which can be seen in
parameter 74 [Motor Spd Est].

Parameter 75 [MtrSpd Est Posit] is an estimated position for sensorless mode. It
is calculated based on [Est Speed Fdbk] and the value in parameter 226 [Virtual
Edge/Rev]. [Virtual Edge/Rev] is a user defined value for the number of pulses
per motor revolution.

Motor Simulator

The simulator mode allows the drive to be operated without a motor connected
and is meant for demo purposes only. If a motor is connected with this mode
selected very erratic and unpredictable operation will occur.

Parameter 76 [MtrSpd Simulated] contains the simulated speed feedback and is
scaled in units of RPM.

Parameter 70 [MtrSpd Sim Posit] contains the simulated position feedback. It is
calculated based on the simulated speed feedback and the value in [Virtual Edge/
Rev]. [Virtual Edge/Rev] is a user defined value for the number of pulses per
motor revolution.

548

74

75

Accum

Σ

Motor Spd Est

226

Virtual Edge/Rev

/

4096

Est Speed Fdbk

MtrSpd Est Posit

76

70

Motor

Simulator

Spd Calc

MtrSpd Simulated

MtrSpd Sim Posit

Accum

Σ

226

Virtual Edge/Rev