Digital outputs, Technical information – Rockwell Automation 20D PowerFlex 700S with Phase I Control Reference Manual User Manual

Page 46

Advertising
background image

46

Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013

Chapter 1

Detail Drive Configuration and Operation

Digital Outputs

Technical Information

There are three digital outputs on the I/O board.

Digital Outputs 1 and 2 are 24VDC open collector (sinking logic). They are
rated 25 mA maximum.

Figure 11 -

is an example of how Digital Outputs 1 and 2

would be used with a light.

Note: The transistor in the diagram is the internal circuitry of the Digital
Output. When the logic for Digital Output 1 becomes true, the transistor turns
on, tying the transistor's collector to ground and completing the circuit. Then the
light will turn on.

Figure 11 - Digital Outputs

Digital Output 3 is a relay output rated for 24VDC. The relay output is rated 5 A
at 24VDC for a resistive load, and 2 A at 24VDC for an inductive load.

Figure 12 - Digital Output Configuration

Digital

Output

Common

(Return)

T6

Sinking

Ouput

G

+ 24V DC

Digital

Output

Logic

T4

841

842

Relay Out Data

Relay Out Bit

16

Local I/O Status
(Output Relay)

TB2-B5

TB2-B4

843

844

Dig Out 1 Data

Data Out 1 Bit

17

Local I/O Status
(Aux Out 1)

TB1-T6

TB1-T5

845

846

Dig Out 2 Data

Data Out 2 Bit

Local I/O Status
(Aux Out 2)

18

TB1-T4

{Return "Common"}

824

824

824

Advertising