Speed Reference Scaling

The first section of the reference selection block is speed reference scaling. Both
speed reference 1 and 2 have parameters associated with them to scale the values.
See

Figure 33

.

Parameter 10 [Speed Ref 1] and parameter 12 [Speed Ref 2] are real parameters
with units of per unit, where a value of 1 per unit equals base motor speed. Both
[Speed Ref 1] and [Speed Ref 2] have their own scaling blocks.

The speed reference value in [Speed Ref 1] is divided by the scaling parameter 11
[Speed Ref1 Divide]. [Speed Ref1 Divide] cannot be changed while running, and
cannot be linked to by another parameter.

The speed reference value for [Speed Ref 2] is multiplied by the scaling parameter
13 [Speed Ref2 Multi]. [Speed Ref2 Multi] is a linkable parameter. This allows
speed reference 2 to be scaled “dynamically” with an input signal if desired. An
example would be to have an analog input linked to the scale parameter. The

10

11

12

0

1

2

3

4

5

6

X

+

13

14

15

16

0

17

1

0

157

00

0

30

31

32

33

34

Inv

Logic

1 0
0 1

157

01

&

157

02

151

00

151

01

0

153

00

37

153

01

35

36

X

38

+

21

61

140

141

144

142

143

151

11

56

9

57

58

Max

X

1

40

1

152

0

47

46

44

180

43

62

63

42

20

Speed Ref 1

Limit

Ramp

S Curve

Spd Ref1 Divide

Speed Ref 2

Spd Ref2 Multi

Speed Ref 4

Speed Ref 5

Speed Ref DPI

Jog Speed 2

Speed Ref Sel

Applied LogicCmd

Logic Ctrl State

Control Options

Applied LogicCmd

Logic

1 0
0 1

41

Rev Speed Limit

Fwd Speed Limit

Selected Spd Ref

Limited Spd Ref

Inertia Comp

Δ

n

Δ

t

Friction Comp

Inertia SpeedRef

InertiaAccelGain

InertiaDecelGain

Total Inertia

Logic Command

(Inertia Comp)

Logic Command

(Frict Comp)

FricComp TorqAdd

FricComp Setup

FricComp Stick

FricComp Slip

FricComp Rated

145

59

45

Delayed Spd Ref

FricComp Spd Ref

Link

Link

Link

Spd Ref Bypass

Control Options

(SRef Filt En)

SpdRef Filt Gain

SpdRef Filt BW

Filtered Spd Ref

Scaled Spd Ref

Spd Trim1 SpdRef

Speed Trim 1

S Curve Spd Ref

Speed Ref Scale

from Process
Control [5G2]

Link

Virtual Encoder

4x internal

Virt Encoder PPR

Virt Encdr Posit

Virt Encdr Dlyed

Ramped Spd Ref

S Curve Time

Accel Time

Decel Time

Logic Command

(SpdRamp Dsbl)

Logic Command

(Spd S Crv En)

Logic Ctrl State

(SRef Ramp En)

Logic Ctrl State

(SRef SCrv En)

Inertia Torq Add

(Unipol Fwd) +1

(Unipol Rev) -1

to Speed Control
- Regulator [3A2]

to Torque

Control [4B2]

to Torque

Control [4B1]

Delay

One

Scan

Delay

One

Scan

/

PI Output

60

DeltaSpeedScale

152

151

10

18

0

18

152

23

Jog Speed 1

0

1

1

55

Speed Comp

Lead Lag

(kn * s)+ wn

s + wn

20

152

21

1

*

set the desired port in
param 691

*

10

11

12

X

13

Speed Ref 1

Spd Ref1 Divide

Speed Ref 2

Spd Ref2 Multi

/